In a workplace the HVAC system is the employer's to inspect. Cal/OSHA's 8 CCR 5142 covers buildings with mechanically driven ventilation: the system is inspected at least annually, what the inspection finds is corrected within a reasonable time, and the inspection and maintenance are documented in writing, naming who did it, the date and the specific findings and actions taken. The employer keeps those records at least five years.
Fire protection systems are held in an operative condition at all times. Where a required system is out of service the fire department and the fire code official are notified immediately. Engineered and pre-engineered fixed extinguishing systems, the family a commercial kitchen hood belongs to, are inspected, tested and maintained at least semi-annually and immediately after a system activation. Local authorities may require more.
The records live on the premises, and they are the first thing anyone asks for. Portable extinguishers are manually inspected when first placed in service and at least monthly after that, or electronically monitored; the date of the manual inspection and the initials of the person who performed it go on a tag or label, an inspection checklist kept on file, or an electronic system. Records of inspections are kept on the premises by the building or system owner for five years after the next required inspection.
Most buildings already hold the list the program starts from. At final inspection the builder leaves maintenance information in the building for the owner, and where a nonresidential building of 10,000 square feet or more was commissioned under the energy standards, a systems manual went to the owner and the facilities operator with it. The backflow assembly's annual date goes on the same calendar.
The round starts from what is in the building: the HVAC units and which spaces they serve, the fire protection systems and their type, any kitchen hood system, the extinguishers and where they hang, and the backflow assemblies. Anything without a document is listed anyway, which is usually where an older building starts.
Maintenance information left at final inspection, a systems manual where the building has one, and the fire and HVAC records already held on the premises are collected and read before anything is scheduled.
The annual inspection is booked, the outdoor air the system was permitted to deliver is checked against what it delivers now, and the written record is completed for the employer.
Hood and other pre-engineered systems on the six-month cycle, water-based systems on the cycle the state has adopted, and the extinguisher round are put on the calendar and coordinated, then carried out by the trade that performs them.
Every extinguisher tag, checklist or electronic record is read for the months that are missing, because that gap is the finding.
A fault goes out as a written scope: HVAC, a failed backflow test, a water heater or a panel to plumbing, electrical and HVAC, and a door, alarm or fitting to commercial property maintenance.
The program does not test or service a system. It holds the date, checks that the work was done and that the record is where it has to be, and sends the work itself to the trade that performs it.
One year of occupancy with no written HVAC record is the common finding, and the maintenance labels left at handover are the checklist nobody has read.
A hood system outside its six-month cycle and extinguisher tags unsigned for months, in suites that change tenant more often than they change equipment.
Large systems and water-based fire protection, with the records kept on the premises and often in a site office nobody has opened this year.
A kitchen with a hood system, many rooms served by one plant, and the employer duty on the HVAC records sitting with the operator.
Backflow assemblies with their own dates and common plant rooms, while alarms and devices inside a dwelling are a repair trade's work.
No manual, no label and no inventory, so the first round writes down what is actually installed before any cycle can be applied to it.
At least annually, with problems corrected within a reasonable time. The inspection and maintenance are documented in writing with the name of the person, the date and the specific findings and actions, and the employer keeps the records at least five years and makes them available within 48 hours of a request.
At least monthly, by manual inspection or electronic monitoring. A manual inspection is recorded with the date and the initials of the person who carried it out, on a tag or label, a checklist kept on file, or an electronic system, and the first inspection happens when the extinguisher is placed in service.
Engineered and pre-engineered fixed extinguishing systems are inspected, tested and maintained at least semi-annually, and immediately after the system has been activated. Wet chemical systems are inspected and tested for proper operation at six-month intervals.
No. Fire system items are scheduled and coordinated here and carried out by the trade that performs them. Water-based systems run on the frequencies the state has adopted, and the local fire authority may require more than that.
The fire department and the fire code official are notified immediately, and the owner or occupant corrects the deficiency or impairment promptly. Both facts go on the record with the date.
Systems rounds are requested through the preventive maintenance page for the city, which names the fire authority whose own requirements go on the calendar.